Compare Current Transformers for Metering

Mini Hinged Learn More Midi Hinged Learn More 150A Clamp On Learn More RoCoil Learn More
Part CT-HSC-020, -050 CT-HMC-100, -200 CT-CON-0150EZ CTR16, R24, R36, R47
Window Size 1 cm (0.4”) 2.5 cm (1.0”) 5.2 cm (1.0”) 16”: 11.5 cm (4.5”) 24”: 17.9 cm (7.0”) 36”: 27.5 cm (10.8”) 47”: 37.0 cm (14.6”)
Output Signal 333 mV at rated current 333 mV at rated current 333 mV @ 150 Amps AC 131 mV/1000A @ 60 Hz 109.2 mV/1000A @ 50 Hz
Useful Current Range 0.25-40 Amps 0.25-80 Amps 1-200 Amps 1-300 Amps .5 to 300 Amps PS3037/PSHD: 5-4000 Amps* EXC: 5-5000 Amps*
Nominal Rating 20, 50 Amps 100, 200 Amps 150 Amps 5000 Amps
Accuracy <0.5% at rated current <1.0% at rated current <1% at rated current <0.6%**
Dimensions 2.6 x 2.9 x 4.2 cm (1.04 x 1.16” x 1.64”) 4.7 x 4.7 x 7.0 cm (1.85 x 1.85 x 2.76”) 8.7 x 5.0 x 1.9 cm (3.4 x 1.9 x 0.8”) Length 16” (40 cm) Length 24” (60 cm) Length 36” (90 cm) Length 47” (120 cm)
Weight 91 g (3.2 oz) 221 g (7.8 oz) 136 g (4.8 oz) 16”: 136 g (5 oz) 24”: 181 g (6 oz) 36”: 227 g (8 oz) 47”: 272 g (10 oz)
Output Lead Leads 2.7 m (8 ft) twisted pair, 20 AWG Leads 2.7 m (8 ft) twisted pair, 22 AWG 2.4 m (8’) 22 gage, 600V 2 m (79”) shielded cable
Safety Requirements UL Recognized: UL STD 61010-1 Certified to: CAN/CSA STD C22.2 No. 61010-1 UL Recognized: UL STD 61010-1 Certified to: CAN/CSA STD C22.2 No. 61010-1 UL Recognized: UL STD 61010-1 Certified to CAN/CSA STD C22.2 No. 61010 Conforms to UL STD 61010-1 Certified to CAN/CSA STD C22.2 No. 61010
Working Voltage Maximum 600 Vrms Category III Maximum 600 Vrms Category III Maximum 600 Vrms Category III Maximum 1000 Vrms Category III