Shop all electrical submetering products
ELITEpro XC![]() Learn More |
|
---|---|
Typical Applications/Usage | Measurement and Verification (M&V) studies, electrical load profiling, energy audits, new technology assessment studies. The ELITEpro XC is typically installed inside an electrical panel for a finite period of time (weeks to months). |
Service Types | Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta), DC Systems (Solar/Battery) |
Voltage Channels | 3 channels, CAT III, 0-600 VAC (line-to-line) or 600 VDC |
Current Channels | 4 channels, .67 VAC max, +/- 1 VDC. Ideal for 333 mV full scale CTs |
Maximum Current Input | External transducer dependent. 200% of current transducer rating (mV CTs) Measure up to 6000A with RoCoil CTs. |
Analog Channels | 4 channels, 0-10 Volts, 0-20 or 4-20 mA current loop. Non-isolated, external power for current loop. User scaling for sensor reporting in physical units. |
Measurement Type | True RMS using high-speed digital signal processing (DSP) |
On Board Memory | 16 MB non-volatile. Depending on the setup table, any measurement can be recorded at the integration period with a time stamp. |
Line Frequency | DC/50/60 Hz |
Waveform Sampling | 12 kHz 200 samples/cycle at 60Hz 240 samples/cycle at 50Hz |
Parameter Update Rate | 8 Hz or every 125 mSec. |
Blind Cycles | 8 Hz or every 125 mSec. |
Integration Period | 1, 3, 15, 30 seconds; 1, 2, 5, 10, 15, 20, and 30 minutes; 1 and 12 hours, 1 day |
Energy Measurements | Volts, Amps, Amp-Hrs (Ah), kW, kWh, kVAR, kVARh, kVA, kVAh, Displacement Power Factor (dPF). All parameters for each phase and for system total. |
Accuracy | Better than 1% (<0.2% typical) for V, A, kW, kVAR, kVA, PF, Analog |
Resolution | 0.01 Amp, 0.001 Volt, 1 Watt, 1 VAR, 1 VA, 0.01 PF, 0.001 Analog |
LED Indicators | Tri-color (red, green, blue): 1 LED indicates communication (blue for wireless, Bluetooth® or Ethernet), 4 LEDs for correct phasing (PhaseChek™). |
Display | None |
Line Power | From L1 Phase to L2 Phase. 80-600V (AC or DC) CAT III DC/50/60 Hz, 125 mA, 5 W, or 10 VA max. Non-user replaceable .5 Amp internal fuse protection. |
Auxiliary Power In | 6-10 VDC, 500 mA |
Power Out | 6 VDC, 200 mA max |
Pulse Output | N/A |
Pulse Input | N/A |
Alarm Output | N/A |
USB | USB standard (Type B). 1.8 M (6 ft) A-to-B USB Cable (included) |
Ethernet | Standard Ethernet. Configure for DHCP or Static IP. |
Bluetooth | Optional. Internal antenna with 10-100 ft range (typical). Requires Bluetooth® wireless technology adapter on Windows PC. Adapter must support the Serial Port Profile (SPP). |
Wi-Fi | Optional. Wi-Fi option available as two separate configurations: • Internal antenna: typical range 75-300 ft. • External 3 dbi antenna: typical range 150-300 ft. |
Modbus | N/A |
BACnet | N/A |
Supported Baud Rates | N/A |
Operating Temperature | -7 to + 60 °C (20 to 140 °F) |
Operating Humidity | 5% to 95% non-condensing |
Enclosure Type | ABS plastic, 94-V0 flammability rating |
Circuit Board Only Option | N/A |
Weight | 340 g (12 ounces) |
Dimensions | (L) 21.6 cm x (W) 6.3 cm x (H) 4.7 cm (8.5” x 2.5” x 1.9”) |
Mounting Options | Mounting tabs or magnets |
UL | UL Listed- Conforms to UL Std 61010-1 Certified to CSA Std C22.2 No. 61010-1 |
CE | EN 61000-6-4: Class A |
ANSI C12.20 Class 0.2 | N/A |
PowerScout 3037![]() Learn More |
---|
Tenant submetering (shopping malls, apartments, office spaces, etc), net metering, data center monitoring or other commercial/industrial applications. The PowerScout 3037 is not meant to be a stand alone energy recorder. They are designed to connect as a slave device to a data logger, Remote Terminal Unit (RTU), or building management host network. |
Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) |
80-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III. |
3 channels, 0.525 VAC max, 333 mV CTs, 0-4,000+ Amps depending on CT |
158% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs |
N/A |
True RMS using high-speed digital signal processing (DSP) |
N/A |
50/60 Hz |
12 kHz |
0.5 seconds |
0.5 seconds |
N/A |
Volts, Amps, kW, kVAR, kVARh, kVA, kVAh, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Import (Received) kVAh, Export (Delivered) kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Frequency. All parameters for each phase and system total. |
0.2% ANSI C12.20-2010 Class 0.2 |
0.01 Amp, 0.1 Volt, 0.01 Watt, 0.01 VAR, 0.01 VA, 0.01 Power Factor depending on scalar setting |
Communications, pulse output, and PhaseChek™ |
Optional 2 x 16 character display which auto-cycles between screens; real-time values updated every second |
From L1 Phase to L2 Phase. 80-600VAC CAT III 50/60Hz, 90mA Max. Non-user replaceable .5 Amp internal fuse protection |
USB |
Unregulated 5VDC output, 140 mA max |
Open Collector, optically isolated, 5mA max current, 30V max open voltage |
N/A |
N/A |
USB standard (Type B). For configuration only. |
Optional Ethernet. Configure for DHCP or Static IP. |
N/A |
N/A |
Modbus RTU (RS-485) or Modbus TCP |
BACnet MS/TP (RS-485) or BACnet IP |
Modbus: 9600 (Default), 19200, 38400, 57600, 76800, 115200 baud BACnet: 9600, 19200, 38400, 57600, 76800 (Default), 115200 |
-7° to 60°C (-20° to 140°F) |
5% to 95% non-condensing |
ABS Plastic, 94-V0 flammability rating |
N/A |
340 g (12 ounces) |
(L) 24.2 cm x (W) 8.5 cm x (H) 4.0 cm (9.5” x 3.3” x 1.6”) |
Mounting tabs or TS35/7 DIN Rail |
UL Listed- Conforms to UL Std 61010-1, 3rd Edition & IEC 61010-2-030 1st edition |
EN 61000-6-4: Class A |
NIST Traceable Calibration |
PowerScout 12 HD![]() Learn More |
---|
Tenant submetering (shopping malls, apartments, office spaces, etc), net metering, data center monitoring or other commercial/industrial applications. The PowerScout 12 HD is not meant to be a stand alone energy recorder. They are designed to connect as a slave device to a data logger, Remote Terminal Unit (RTU), or building management host network. |
Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) |
90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III. |
12 channels, 0.525 VAC max, 333 mV CTs, 0-4,000 Amps depending on CT |
150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs |
N/A |
True RMS using high-speed digital signal processing (DSP) with continuous sampling |
Energy (kWh) values are recorded every 15 minutes for 63 days (downloadable log) Each record is time stamped |
50/60 Hz (45-70 Hz measurable range). Measurement taken L1-N. |
1.8 kHz |
1 second |
None |
15 minutes |
Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and element total. |
0.2% ANSI C12.20-2010 Class 0.2 |
Values in IEEE-754 single precision floating point format (32 bit). |
N/A |
Optional 4-line display, tri-color backlight (PhaseChek™) |
From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max. Use of 12 volt auxiliary output requires 100 VAC minimum input voltage. |
USB |
Unregulated 12VDC output, 200 mA, self-resetting fuse. |
N/A |
Four inputs. 3.3V sourcing voltage (current limited) to customer dry contact pulse output. Max pulse rate 10 Hz (50 mSec minimum transition time). |
Over/Under Voltage & Current (SPDT Relay - 30 VDC) |
USB standard (Type B). For configuration only or downloading of logged data. |
Standard Ethernet. Configure for DHCP or Static IP. |
N/A |
N/A |
Modbus RTU (RS-485) or Modbus TCP |
BACnet MS/TP (RS-485) or BACnet IP |
9600 (Default), 19200, 38400, 57600, 76800, 115200 |
-20° to 60°C (-4° to 140°F) |
5% to 95% non-condensing |
ABS Plastic, 94-V0 flammability rating. Connections: 1” EMT conduit |
Circuit board on mounting plate available |
1043 g - 1452 g (2.3 - 3.2 lbs) depending on configuration |
Enclosure: (L) 24.8cm x (W) 25.1cm x (H) 8.0 cm (9.8” x 9.8” x 3.1”) Mounting Plate: (L) 17.8cm x (W) 26.3cm x (H) 8.0 cm (7.0” x 10.4” x 3.1”) |
Panel Mount/Enclosure |
Circuit Board on Plate: UL Recognized-Conforms to UL Std 61010-1 3rd Edition Certified to CSA Std C22.2 No. 61010-1 3rd Edition Enclosure Version: UL Listed-Conforms to UL Std 61010-1 3rd Edition Certified to CSA Std C22.2 No. 61010-1 3rd Edition |
EN 61000-6-4: Class A |
NIST Traceable Calibration |
PowerScout 48 HD![]() Learn More |
---|
Tenant submetering (shopping malls, apartments, office spaces, etc), net metering, data center monitoring or other commercial/industrial applications. The PowerScout 48 HD is not meant to be a stand alone energy recorder. They are designed to connect as a slave device to a data logger, Remote Terminal Unit (RTU), or building management host network. |
Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) |
90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III. Two voltage reference inputs. |
48 channels, 0.525 VAC max, 333 mV CTs, 0-4,000 Amps depending on CT |
150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs |
N/A |
True RMS using high-speed digital signal processing (DSP) with continuous sampling |
Energy (kWh) values are recorded every 15 minutes for 63 days (downloadable log) Each record is time stamped |
50/60 Hz (45-70 Hz measurable range). Measurement taken L1-N. |
1.8 kHz |
1 second |
None |
15 minutes |
Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and element total. |
0.2% ANSI C12.20-2010 Class 0.2 |
Values in IEEE-754 single precision floating point format (32 bit). |
N/A |
Optional 4-line display, tri-color backlight (PhaseChek™) |
From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max. Use of 12 volt auxiliary output requires 100 VAC minimum input voltage. |
USB |
Unregulated 12VDC output, 200 mA, self-resetting fuse. |
N/A |
Two inputs. 3.3V sourcing voltage (current limited) to customer dry contact pulse output. Max pulse rate 10 Hz (50 mSec minimum transition time). |
Over/Under Voltage & Current (SPDT Relay - 30 VDC) |
USB standard (Type B). For configuration only or downloading of logged data. |
Standard Ethernet. Configure for DHCP or Static IP. |
N/A |
N/A |
Modbus RTU (RS-485) or Modbus TCP |
BACnet MS/TP (RS-485) or BACnet IP |
9600 (Default), 19200, 38400, 57600, 76800, 115200 |
-20° to 60°C (-4° to 140°F) |
5% to 95% non-condensing |
ABS Plastic, 94-V0 flammability rating. Connections: 1” EMT conduit |
Circuit board on mounting plate available |
1814 g - 2223 g (4.0 - 4.9 lbs) depending on configuration |
Enclosure: (L) 33.7cm x (W) 25.1cm x (H) 8.0 cm (13.3” x 9.8” x 3.1”) Mounting Plate: (L) 26.2cm x (W) 24.1cm x (H) 8.0 cm (10.3” x 9.5” x 3.1”) |
Panel Mount/Enclosure |
Circuit Board on Plate: UL Recognized- Conforms to UL Std 61010-1 3rd Edition Certified to CSA Std C22.2 No. 61010-1 3rd Edition Enclosure Version: UL Listed- Conforms to UL Std 61010-1 3rd Edition Certified to CSA Std C22.2 No. 61010-1 3rd Edition |
EN 61000-6-4: Class A |
NIST Traceable Calibration |