PowerScout Comparison

  ELITEpro XC

ps-compare-elitepro

Learn More
Typical Applications/Usage  
 
 
 
Measurement and Verification (M&V) studies, electrical load profiling, energy audits, new technology assessment studies. The ELITEpro XC is typically installed inside an electrical panel for a finite period of time (weeks to months).
Service Types Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta), DC Systems (Solar/Battery)
Voltage Channels  
3 channels, CAT III, 0-600 VAC (line-to-line) or 600 VDC
Current Channels 4 channels, .67 VAC max, +/- 1 VDC. Ideal for 333 mV full scale CTs
Maximum Current Input External transducer dependent.
200% of current transducer rating (mV CTs)
Measure up to 6000A with RoCoil CTs.
Analog Channels 4 channels, 0-10 Volts, 0-20 or 4-20 mA current loop. Non-isolated, external power for current loop. User scaling for sensor reporting in physical units.
Measurement Type  
True RMS using high-speed digital signal processing (DSP)
On Board Memory 16 MB non-volatile. Depending on the setup table, any measurement can be recorded at the integration period with a time stamp.
Line Frequency  
DC/50/60 Hz
Waveform Sampling 12 kHz
200 samples/cycle at 60Hz
240 samples/cycle at 50Hz
Parameter Update Rate 8 Hz or every 125 mSec.
Blind Cycles 8 Hz or every 125 mSec.
Integration Period 1, 3, 15, 30 seconds; 1, 2, 5, 10, 15, 20, and 30 minutes; 1 and 12 hours, 1 day
Energy Measurements  
 
 
 
 
Volts, Amps, Amp-Hrs (Ah), kW, kWh, kVAR, kVARh, kVA, kVAh, Displacement Power Factor (dPF). All parameters for each phase and for system total.
Accuracy Better than 1% (<0.2% typical) for V, A, kW, kVAR, kVA, PF, Analog
Resolution  
0.01 Amp, 0.001 Volt, 1 Watt, 1 VAR, 1 VA, 0.01 PF, 0.001 Analog
LED Indicators Tri-color (red, green, blue): 1 LED indicates communication (blue for wireless, Bluetooth® or Ethernet), 4 LEDs for correct phasing (PhaseChek™).
Display  
 
 
None
Line Power From L1 Phase to L2 Phase. 80-600V (AC or DC) CAT III DC/50/60 Hz, 125 mA, 5 W, or 10 VA max. Non-user replaceable .5 Amp internal fuse protection.
Auxiliary Power In 6-10 VDC, 500 mA
Power Out  
6 VDC, 200 mA max
Pulse Output  
 
N/A
Pulse Input  
 
 
 
N/A
Alarm Output  
N/A
USB  
USB standard (Type B). 1.8 M (6 ft) A-to-B USB Cable (included)
Ethernet Standard Ethernet. Configure for DHCP or Static IP.
Bluetooth Optional. Internal antenna with 10-100 ft range (typical). Requires Bluetooth® wireless technology adapter on Windows PC. Adapter must support the Serial Port Profile (SPP).
Wi-Fi Optional. Wi-Fi option available as two separate configurations:
• Internal antenna: typical range 75-300 ft.
• External 3 dbi antenna: typical range 150-300 ft.
Modbus  
N/A
BACnet  
N/A
Supported Baud Rates  
 
 
 
N/A
Operating Temperature -7 to + 60 °C (20 to 140 °F)
Operating Humidity 5% to 95% non-condensing
Enclosure Type  
ABS plastic, 94-V0 flammability rating
Circuit Board Only Option  
N/A
Weight  
340 g (12 ounces)
Dimensions  
 
 
(L) 21.6 cm x (W) 6.3 cm x (H) 4.7 cm (8.5” x 2.5” x 1.9”)
Mounting Options Mounting tabs or magnets
UL  
 
 
 
 
 
UL Listed- Conforms to UL Std 61010-1
Certified to CSA Std C22.2 No. 61010-1
CE EN 61000-6-4: Class A
ANSI C12.20 Class 0.2 N/A
PowerScout 3037

ps-compare-ps3037

Learn More
Tenant submetering (shopping malls, apartments, office spaces, etc), net metering, data center monitoring or other commercial/industrial applications. The PowerScout 3037 is not meant to be a stand alone energy recorder. They are designed to connect as a slave device to a data logger, Remote Terminal Unit (RTU), or building management host network.
 
Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta)
 
80-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III.
3 channels, 0.525 VAC max, 333 mV CTs, 0-4,000+ Amps depending on CT
 
158% of current transducer rating (mV CTs) to maintain accuracy.
Measure up to 4000A with RōCoil CTs
 
 
 
 
N/A
 
True RMS using high-speed digital signal processing (DSP)
 
 
 
N/A
 
50/60 Hz
 
 
12 kHz
0.5 seconds
0.5 seconds
 
 
N/A
 
Volts, Amps, kW, kVAR, kVARh, kVA, kVAh, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Import (Received) kVAh, Export (Delivered) kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Frequency. All parameters for each phase and system total.
 
0.2% ANSI C12.20-2010 Class 0.2
0.01 Amp, 0.1 Volt, 0.01 Watt, 0.01 VAR, 0.01 VA, 0.01 Power Factor depending on scalar setting
 
 
 
Communications, pulse output, and PhaseChek™
Optional 2 x 16 character display which auto-cycles between screens; real-time values updated every second
 
From L1 Phase to L2 Phase. 80-600VAC CAT III 50/60Hz, 90mA Max. Non-user replaceable .5 Amp internal fuse protection
USB
Unregulated 5VDC output, 140 mA max
Open Collector, optically isolated, 5mA max current, 30V max open voltage
 
 
 
 
N/A
 
N/A
 
USB standard (Type B). For configuration only.
Optional Ethernet. Configure for DHCP or Static IP.
 
 
 
 
 
N/A
 
 
 
 
 
N/A
Modbus RTU (RS-485) or Modbus TCP
BACnet MS/TP (RS-485) or BACnet IP
Modbus: 9600 (Default), 19200, 38400, 57600, 76800, 115200 baud
BACnet: 9600, 19200, 38400, 57600, 76800 (Default), 115200
-7° to 60°C (-20° to 140°F)
5% to 95% non-condensing
 
ABS Plastic, 94-V0 flammability rating
 
N/A
 
340 g (12 ounces)
 
 
 
(L) 24.2 cm x (W) 8.5 cm x (H) 4.0 cm (9.5” x 3.3” x 1.6”)
Mounting tabs or TS35/7 DIN Rail
 
 
 
 
 
 
 
UL Listed- Conforms to UL Std 61010-1, 3rd Edition & IEC 61010-2-030 1st edition
EN 61000-6-4: Class A
NIST Traceable Calibration
PowerScout 12 HD

ps-compare-ps12hd

Learn More
Tenant submetering (shopping malls, apartments, office spaces, etc), net metering, data center monitoring or other commercial/industrial applications. The PowerScout 12 HD is not meant to be a stand alone energy recorder. They are designed to connect as a slave device to a data logger, Remote Terminal Unit (RTU), or building management host network.
 
Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta)
 
90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III.
12 channels, 0.525 VAC max, 333 mV CTs, 0-4,000 Amps depending on CT
 
150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs
 
 
 
 
N/A
True RMS using high-speed digital signal processing (DSP) with continuous sampling
Energy (kWh) values are recorded every 15 minutes for 63 days (downloadable log) Each record is time stamped
50/60 Hz (45-70 Hz measurable range). Measurement taken L1-N.
 
 
1.8 kHz
1 second
None
 
 
15 minutes
Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and element total.
 
0.2% ANSI C12.20-2010 Class 0.2
 
Values in IEEE-754 single precision floating point format (32 bit).
 
 
 
 
N/A
 
 
Optional 4-line display, tri-color backlight (PhaseChek™)
From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max. Use of 12 volt auxiliary output requires 100 VAC minimum input voltage.
USB
Unregulated 12VDC output, 200 mA, self-resetting fuse.
 
 
N/A
Four inputs. 3.3V sourcing voltage (current limited) to customer dry contact pulse output. Max pulse rate 10 Hz (50 mSec minimum transition time).
Over/Under Voltage & Current (SPDT Relay - 30 VDC)
USB standard (Type B). For configuration only or downloading of logged data.
Standard Ethernet. Configure for DHCP or Static IP.
 
 
 
 
 
N/A
 
 
 
 
 
N/A
Modbus RTU (RS-485) or Modbus TCP
BACnet MS/TP (RS-485) or BACnet IP
 
 
 
9600 (Default), 19200, 38400, 57600, 76800, 115200
-20° to 60°C (-4° to 140°F)
5% to 95% non-condensing
ABS Plastic, 94-V0 flammability rating. Connections: 1” EMT conduit
Circuit board on mounting plate available
1043 g - 1452 g (2.3 - 3.2 lbs) depending on configuration
Enclosure: (L) 24.8cm x (W) 25.1cm x (H) 8.0 cm (9.8” x 9.8” x 3.1”)
Mounting Plate: (L) 17.8cm x (W) 26.3cm x (H) 8.0 cm (7.0” x 10.4” x 3.1”)
Panel Mount/Enclosure
Circuit Board on Plate: UL Recognized-Conforms to UL Std 61010-1 3rd Edition
Certified to CSA Std C22.2 No. 61010-1 3rd Edition
Enclosure Version: UL Listed-Conforms to UL Std 61010-1 3rd Edition
Certified to CSA Std C22.2 No. 61010-1 3rd Edition
EN 61000-6-4: Class A
NIST Traceable Calibration
PowerScout 48 HD

ps-compare-ps48hd

Learn More
Tenant submetering (shopping malls, apartments, office spaces, etc), net metering, data center monitoring or other commercial/industrial applications. The PowerScout 48 HD is not meant to be a stand alone energy recorder. They are designed to connect as a slave device to a data logger, Remote Terminal Unit (RTU), or building management host network.
 
Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta)
90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III. Two voltage reference inputs.
48 channels, 0.525 VAC max, 333 mV CTs, 0-4,000 Amps depending on CT
 
150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs
 
 
 
 
N/A
True RMS using high-speed digital signal processing (DSP) with continuous sampling
Energy (kWh) values are recorded every 15 minutes for 63 days (downloadable log) Each record is time stamped
50/60 Hz (45-70 Hz measurable range). Measurement taken L1-N.
 
 
1.8 kHz
1 second
None
 
 
15 minutes
Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and element total.
 
0.2% ANSI C12.20-2010 Class 0.2
 
Values in IEEE-754 single precision floating point format (32 bit).
 
 
 
 
N/A
 
 
Optional 4-line display, tri-color backlight (PhaseChek™)
From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max. Use of 12 volt auxiliary output requires 100 VAC minimum input voltage.
USB
Unregulated 12VDC output, 200 mA, self-resetting fuse.
 
 
N/A
Two inputs. 3.3V sourcing voltage (current limited) to customer dry contact pulse output. Max pulse rate 10 Hz (50 mSec minimum transition time).
Over/Under Voltage & Current (SPDT Relay - 30 VDC)
USB standard (Type B). For configuration only or downloading of logged data.
Standard Ethernet. Configure for DHCP or Static IP.
 
 
 
 
 
N/A
 
 
 
 
 
N/A
Modbus RTU (RS-485) or Modbus TCP
BACnet MS/TP (RS-485) or BACnet IP
 
 
 
9600 (Default), 19200, 38400, 57600, 76800, 115200
-20° to 60°C (-4° to 140°F)
5% to 95% non-condensing
ABS Plastic, 94-V0 flammability rating. Connections: 1” EMT conduit
Circuit board on mounting plate available
1814 g - 2223 g (4.0 - 4.9 lbs) depending on configuration
Enclosure: (L) 33.7cm x (W) 25.1cm x (H) 8.0 cm (13.3” x 9.8” x 3.1”)
Mounting Plate: (L) 26.2cm x (W) 24.1cm x (H) 8.0 cm (10.3” x 9.5” x 3.1”)
Panel Mount/Enclosure
Circuit Board on Plate: UL Recognized- Conforms to UL Std 61010-1 3rd Edition
Certified to CSA Std C22.2 No. 61010-1 3rd Edition
Enclosure Version: UL Listed- Conforms to UL Std 61010-1 3rd Edition
Certified to CSA Std C22.2 No. 61010-1 3rd Edition
EN 61000-6-4: Class A
NIST Traceable Calibration