|
| |
|
ELITEpro
SP |
SMARTloggers
| Software/Communications
PowerScout |
ELITEpro
and DATApro |
|
General
Questions
|
-
What's the difference between displacement and apparent
power factor? Displacement power factor is the ratio of
the fundamental (60 Hz) real power to apparent power. Apparent power
factor is a ratio of total real power (including harmonic component) to
apparent power.
-
How can there be a Power Factor of .87 on a 3-Phase Delta
lighting load? The line currents in a delta are shifted 30°
compared to the line-line voltage. One line current will be shifted +30°
and the other line current shifted -30° when compared to the line-line
voltage. Since power factor is COS(theta), then COS 30° = .866. This will
be true for the hardware channels. If the power sum channel (5 or 6) is used,
the power factor for the whole load should be as expected.
-
Why am I seeing negative Watts on one phase of a 3-Phase
Delta system? The line currents in a delta are shifted 30°
compared to the line-line voltage. When connected to a load that has a PF of
<.5 (>60°) (e.g. a motor not fully loaded) one line current becomes
shifted >90° (30° +>60°) when compared to the line-line
voltage. The other phase is shifted >30° (-30° + >60°). The
COS of an angle >90° is negative, therefore WATTs = COS(theta)VA is
negative for that phase. However, as with the power factor the sum of the
watts in a delta should be positive. If not, check the CT orientation, one or
both may be reversed. Also check to make sure the CT’s are referenced to
the correct line voltages.
-
Can I use the software to assist in verifying a current
transformer connection? Yes. If no current transformer is
connected to a channel that is turned on, then a non-zero reading will be
displayed. If the CT is connected but shows a '0' for a value, then the
CT is probably connected but the monitored load is turned off. On the
other hand if a constant value for current is displayed, a CT wire may have
come off of the logger.
- Is the battery on my DENT
ELITEpro/DATApro/SMARTlogger rechargeable? No. These DENT loggers have single-use
Lithium cell batteries that cannot be recharged and should be disposed of
properly. Please contact DENT Instruments for replacement
batteries.
Top of
Page |
|
ELITEpro SP
Instruments
|
|
- I'm having trouble
installing the driver for my ELITEpro SP. How do I correct this
issue? Detailed instructions can be found on our Tech Help
page. Please click here to get to the PDF instruction sheet.
- How do I update the
firmware in my ELITEpro SP? Current firmware files and instructions can be
found on the Downloads page. Please click here to visit the download page.
- Is ELOG 11 compatible
with Windows 7 64-bit? ELOG 11 is compatible with Windows 7 32 and 64 bit
operating systems. It is also compatible with Vista 32 and 64 bit and Windows
XP.
- Which CTs can I use
with my ELITEpro SP? The ELITEpro SP is compatible with any split-core,
clamp-on, or flexible RoCoil CT found on the DENT website. Any CTs that are
compatible with the legacy ELITEpro instrument are also compatible with the
ELITEpro SP.
- Does the ELITEpro SP
have an internal battery? The ELITEpro SP does have an internal battery, but
it is only for powering the logger's internal clock--it does not power the
ELITEpro SP. The ELITEpro SP is line powered, but maybe also be powered from a
USB connection or from a wall adapter (sold seperately).
- What is the typical
lifespan of the clock battery? The typical battery life is 5 years. This battery
is user replaceable and can easily be found at an electronics
store.
|
|
| ELITEpro and DATApro
Instruments
(DISCONTINUED) |
|
|
Top of
Page |
|
SMARTlogger Instruments
|
|
|
Top of
Page |
|
|
Software/Communications |
|
- Which operating systems are
ELOG, SMARTware and ViewPoint compatible with?
ELOG 11, SMARTware 11, and
ViewPoint are all compatible with Windows 7 (32 and 64 bit), Windows Vista (32
and 64 bit), and Windows XP.
- I've installed ELOG on my
Windows 2000 PC, but the program will not start. It says that I'm missing a
.dll file. Some Windows 2000 computers
are missing the "gdiplus.dll." Please download this file
here or from the
Support Documents page of this website and
place it in the main SMARTware folder on your hard
drive.
- The
"Total Usage (channel 5) KWh" reported in the Data File Summary does not
exactly match the individual channel 5 KWh "Total"
number--why? The "Total Usage (channel 5)" value is only
updated once per minute. If your integration period is set to less than one
minute, channel 5 KWh "Total" column will aquire data that has not been added
to the "Total Usage (channel 5)" value. (For example, if your logger is set to
15 second integration and you aquire 1.5 minutes of data--or 6 intervals--that
"Total Usage (channel 5)" will not include the final 2 recorded data
points.)
- How
do I scale the graphs to suit my purposes in the
software? By double clicking on the Y or X
axis.
- How
do I zoom-in when working with ELOG software? Simply position
the mouse pointer near the area to be zoomed. Hold the Control (Ctrl) key
and left mouse button down at the same time, then drag the pointer to make a
rectangle that covers the area to be zoomed. Let go of the mouse and
Control Key and the graph will redraw a zoomed portion of the graph. The
graph may be zoomed as many times as desired. Use the View > UnZoom
(Ctrl U), or the key to unzoom, to zoom out again.
- When I am monitoring a load that requires more than one channel
(such as a 3 Phase - 3 Wire Delta load) which channel shows my totals in my
ELOG™ software? When using more than one channel
for one load, the results from each channel need to be added together to obtain
the total power consumption. This is done using the computed channels 5
and 6.
-
Do I need software,
and does it have to be ordered separately? Yes, software is used to program and start the
PRO series (ELOG™ software) and SMARTlogger™ (SMARTware™
software) series instruments, in addition to retrieving and analyzing the
collected data. If multiple loggers are used, there may not be a need for
multiple copies of the software as the software comes with an unlimited site
license.
ELITEpro SP instruments come with a copy of ELOG 11 software. You do not need
to purchase the software separately in this case.
- Can I order
the communication cables separately? Yes, the communications cable can
be ordered separately or as part of the communication package.
Communication cables for the weather-tight enclosure are special and must be
ordered specifically when needed.
- Once I have
the data, can I export it to a spreadsheet or
database? Yes, data can easily be exported to any ASCII
programs like Excel® or Access®.
- How will I
know if I have sufficient memory to complete my
study? The first page of the 'set-up' table automatically
calculates memory capacity allowing the user to do
'what-if's'.
- Is the
software the same for the ELITEpro™ and the
DATApro™? Yes, the ELOG™
software is used for both instruments.
- Is the
software the same for all the
SMARTloggers™? Yes, the
SMARTware™ software is used for all
SMARTlogger™
instruments.
Top of
Page |
|
PowerScout Instruments
|
|
- What is the maximum distance
for Modbus communication?
Modbus can reach a
distance up to 1200 yards with data rates at 100
kbps.
- What is the purpose of
setting a scalar value? Each Modbus register is only
16 bits wide and is in integer format without any fixed number of decimal
points. Simply putting a value directly into one of these registers would limit
the smallest number to be 1, and only allow for a maximum value of 65535. To
handle larger numbers, or numbers with better resolution, we use a scalar value
that is used to apply a factor to the 16-bit register
value.
- One (or more) of the PhaseChek LEDs is red. What does this
mean? Any number of red lights
indicates the PowerScout is wired incorrectly. Review the table in the
PhaseChek section of the
manual for a description of the indicator lights.
-
How is the PowerScout powered? All
PowerScout instruments are line-powered. An internal power supply attached
between L1 and L2 provides power to the unit.
- How many PowerScout 3 instruments can be connected
together? Up to 254 PowerScout 3 meters can be connected
together if they are using Modbus for communications. Up to 127 PowerScout 3 meters may be connected together if they are communicating via BACnet..
- How is hexadecimal (HEX) to decimal converted?
Use the Hexadecimal to Decimal conversion table in the Appendix section of the
PowerScout manual.
- What is true
RMS? RMS stands for "Root-Mean-Square." True RMS is
the Ac voltage/current that will produce the equivalent amount of heat in a
resistor as a DC voltage/current, whether sinusoidal or not. For example, if a
resistive heating element is rated at 15 kW of heat at 240VAC RMS, then the
heat would be the same if we applied 240V of DC instead of AC. A meter without
true RMS will incorrectly read distorted waveforms. All DENT
Instruments'
meters measure true RMS.
-
How accurate is the
PowerScout 3? The PowerScout 3 accuracy is
greater than 1%.
-
What is the maximum distance
for RoCoil CTs? The maximum distance for RoCoils is 100
ft.
- Can a 3-phase balanced load
be monitored with one CT? This is not the best way to measure a three phase
load, but there is an Amp Multiplier register (44605) that can be set for three
which will multiply the current by three and, therefore, amps, watts, VA, and
VARs will be three times greater.
Top of
Page |
|
|
|
|
|
|
|
|